PRIOLION Safety Cabinet for Lithium-ion Batteries

Download

PRIOLION Safety Cabinet for Lithium-ion Batteries

Function

  • Tested fire protection

  • Tested fire resistance of 90 minutes from the outside to the inside according to DIN EN 14470-1

  • Max. temperature rise in the interior at no temperature measuring point more than 100 K

  • Tested fire resistance of 90 minutes from inside to outside according to DIN EN 1363-2

  • GS mark - tested according to test principle EK5/AK4 22-01

  • Self-closing doors tested for continuous use

  • Suitable for the storage and charging of lithium-ion batteries

  • Suitable for the storage of critical batteries (deformation, leakage of liquids, increased temperature above 40°C).

  • Internal real fire test of an equipped cabinet

 

Structure & equipment

  • Safety cabinet with high-quality surface inside and outside

  • Permanently self-closing doors with oil-damped door closers

  • Double-leaf version, double traffic leaf with centre bar

  • Each door can be operated with one hand

  • Cupboard doors close automatically from any position

  • Doors lockable with profile cylinder (lockable)

  • Incl. technical ventilation (to avoid heat accumulation in the interior)

  • Closure of supply and exhaust air in case of fire, triggering via thermocouple and smoke detector

  • Integrated pedestal that can be moved underneath, height 100 mm with removable pedestal cover, thus easy change of location possible

  • Base cover included in scope of delivery

  • Four height-adjustable gratings, max. load 75 kg/floor

  • Integrated liquid-tight base tray (powder-coated sheet steel) to absorb any leakage that may occur.

  • Each storage level can be equipped with a socket strip incl. 10 protective contact sockets

  • Ready to plug in for connection to the mains supply

  • With control unit as standard (visual and acoustic status indication)

  • Smoke detector inside the cupboard automatically triggers in case of fire

  • Optional fire suppression system

  • A potential-free interface is available for connecting a signal (e.g. to a control centre).

  • Complete disconnection of the power supply to the cabinet

 

Technical Specifications

  • Dimensions H x W x D external 1950 x 1200 x 595 mm

  • Entry width transport pedestal 1084 mm

  • Entry height transport pedestal 100 mm

  • Power consumption operation max. 50 W

  • Rated voltage 230 V

  • Frequency 50 Hz