Model
|
Housing dimensions not incl. fittings and connections
W x H x D
[mm] |
Internal dimension
W x H x D
[mm] |
Net weight
[kg] |
Interior volume
[L] |
MK 56 |
720 x 1445 x 778 |
400 x 420 x 350 |
168 |
60 |
MK 115 |
980 x 1725 x 865 |
600 x 480 x 400 |
260 |
115 |
MK 240 |
1115 x 1710 x 925 |
735 x 700 x 443 |
340 |
228 |
MK 720 |
1580 x 2005 x 1140 |
1200 x 1020 x 600 |
570 |
734 |
MK 56 Dynamic climate chambers for rapid temperature changes BINDER
Technical Data
Average cooling down time according to IEC 60068-3-5 [K/min] 5
Average heating-up rate according to IEC 60068-3-5 [K/min] 5
Cooling down time from 180 °C to -40 °C [min] 90
Max. heat compensation at 25 °C [W] 800
Temperature fluctuation depending on setpoint [± K] 0.1…0.5
Temperature range [°C] -40…180
Temperature variation depending on setpoint [± K] 0.5…1.5
Nominal power [kW] 2.8
Phase (Nominal voltage) 1~
Power frequency [Hz] 50
Rated Voltage [V] 230
Unit fuse [A] 16
Unit doors 1
Depth [mm] 350
Height [mm] 420
Width [mm] 400
Interior volume [L] 60
Load per rack [kg] 15
Net weight of the unit (empty) [kg] 168
permitted load [kg] 60
Depth net [mm] 778
Height net [mm] 1445
Viewing window height [mm] 255
Viewing window width [mm] 288
Wall clearance back [mm] 300
Wall clearance sidewise [mm] 200
Width net [mm] 720
Sound-pressure level [dB(A)] 59
Number of shelves (std./max.) 1/4
MK 115 Dynamic climate chambers for rapid temperature changes BINDER
Technical Data
Average cooling down time according to IEC 60068-3-5 [K/min] 5
Average heating-up rate according to IEC 60068-3-5 [K/min] 5.3
Cooling down time from 180 °C to -40 °C [min] 90
Max. heat compensation at 25 °C [W] 1500
Temperature fluctuation depending on setpoint [± K] 0.1…0.5
Temperature range [°C] -40…180
Temperature variation depending on setpoint [± K] 0.1…2
Nominal power [kW] 3.5
Phase (Nominal voltage) 3~
Power frequency [Hz] 50
Rated Voltage [V] 400
Unit fuse [A] 16
Unit doors 1
Depth [mm] 400
Height [mm] 480
Width [mm] 600
Interior volume [L] 115
Load per rack [kg] 30
Net weight of the unit (empty) [kg] 260
permitted load [kg] 60
Depth net [mm] 865
Height net [mm] 1725
Viewing window height [mm] 222
Viewing window width [mm] 288
Wall clearance back [mm] 300
Wall clearance sidewise [mm] 200
Width net [mm] 980
Sound-pressure level [dB(A)] 62
Number of shelves (std./max.) 1/4
MK 240 Dynamic climate chambers for rapid temperature changes BINDER
Technical Data
Average cooling down time according to IEC 60068-3-5 [K/min] 4.5
Average heating-up rate according to IEC 60068-3-5 [K/min] 5
Cooling down time from 180 °C to -40 °C [min] 110
Max. heat compensation at 25 °C [W] 2000
Temperature fluctuation depending on setpoint [± K] 0.1…0.5
Temperature range [°C] -40…180
Temperature variation depending on setpoint [± K] 0.1…1.2
Nominal power [kW] 5.6
Phase (Nominal voltage) 3~
Power frequency [Hz] 50
Rated Voltage [V] 400
Unit fuse [A] 16
Unit doors 1
Depth [mm] 443
Height [mm] 700
Width [mm] 735
Interior volume [L] 228
Load per rack [kg] 30
Net weight of the unit (empty) [kg] 340
permitted load [kg] 70
Depth net [mm] 925
Height net [mm] 1710
Viewing window height [mm] 300
Viewing window width [mm] 508
Wall clearance back [mm] 300
Wall clearance sidewise [mm] 200
Width net [mm] 1115
Sound-pressure level [dB(A)] 62
Number of shelves (std./max.) 1/6
MK 720 Dynamic climate chambers for rapid temperature changes BINDER
Technical Data
Average cooling down time according to IEC 60068-3-5 [K/min] 4.5
Average heating-up rate according to IEC 60068-3-5 [K/min] 4
Max. heat compensation at 25 °C [W] 3500
Temperature fluctuation depending on setpoint [± K] 0.1…0.5
Temperature range [°C] -40…180
Temperature variation depending on setpoint [± K] 0.3…2
Nominal power [kW] 8.7
Phase (Nominal voltage) 3~
Power frequency [Hz] 50
Rated Voltage [V] 400
Unit fuse [A] 16
Unit doors 1
Depth [mm] 600
Height [mm] 1020
Width [mm] 1200
Interior volume [L] 734
Load per rack [kg] 40
Net weight of the unit (empty) [kg] 570
permitted load [kg] 160
Depth net [mm] 1140
Height net [mm] 2005
Viewing window height [mm] 300
Viewing window width [mm] 508
Wall clearance back [mm] 300
Wall clearance sidewise [mm] 200
Width net [mm] 1580
Sound-pressure level [dB(A)] 65
Number of shelves (std./max.) 1/11